Technical data

General data and operating conditions

EDKMF2133 DE/EN/FR 6.1

66

l

H1_Daten−protokollDat

6

Technical data

General data and operating conditions

Communication−relevant data

Values

Communication media

RS 485

Network topology

without repeater: line / with repeater: line or tree

Number of devices

Standard: 32 (= 1 bus segment) / with repeaters: 125

Cable length / segment

1200 m
(depending on the baud rate and the cable type used)

Communication profile

PROFIBUS−DP
(DIN 19245 part 1 and part 3)

PUO ID number

2133

hex

Drive profile

l

DRIVECOM profile "Power Transmission 20", can be switched off

l

PROFIDRIVE version 2, can be switched off
(status machine and PIV interface)

PROFIBUS participants

Slave

Baud rate for cable type A (EN
50170)

9.6 kbits/s up to 12 Mbits/s (automatically detected)

Process data words (PCD),
16 bits

1 word ... 12 words

DP user data length

Parameter data channel (4 words) +
process data words (1 .... 12 words)

External voltage supply

Values

"+"

V = 24 V DC (21.6 V − 0% ... 26.4 V + 0 %)

I = 120 mA

"−"

Reference potential for external voltage supply

Operating conditions

Values

Deviations from standard

Climatic conditions

Storage 1 K3 to IEC/EN 60721−3−1

−25 °C ... + 60 °C

Transport 2 K3 to IEC/EN 60721−3−2

Operation 3 K3 to IEC/EN 60721−3−3

0 °C ... + 55 °C

Enclosure

IP20

Degree of pollution

2 to IEC/EN 61800−5−1