Commissioning

Addressing

5

EDKMF2133 DE/EN/FR 6.1

63

l

H2 Adressierung−SetSlaveAdress

Address settings through keypad or PC

Addresses are set using code C0009 (see controller code table)

DIP switches S1 − S7 must be in OFF position (= delivery state).

Address settings through the master class 2

With this method only one device must be connected to the bus. This can be achieved by a
special switch−on sequence.

Settings made through the master (master class 2) have an effect on the setting in code
C0009.

PROFIBUS station address

Mapping to code C0009 (LECOM node address)

1−2

No (master addresses)

3−99

Yes (3−99)

100−125

Yes (C0009=2)

126 (LENZE setting)

Yes (C0009=1)

Tab. 1

Assignment of station addresses to controllers

)

Note!

In the "Power On" status, the class 2 master can set a device address via the
"Set_Slave_Address" telegram.