Preliminary works

Coding by setting the DIP switches

EDK2174DB DE/EN/FR 3.0

10

H2WichtHinw-Codierung_DIP_en

Coding by setting the DIP switches

Remove the front plate of the CAN addressing module in order to set the baud rate and the

controller address in its interior with DIP switches.

Left DIP switch

(S1L, S2L, S3L, S4L, S5L)

Right DIP switch

(S1R, S2R, S3R, S4R, S5R)

2174CAN005

Setting the baud rate
SetthebaudratewiththeswitchesS1L,S2LandS3L. Theswitchsettingsrequiredforsetting

the baud rate are represented in the following table:

Baud rate

S1L

S2L

S3L

[kbaud]

500

OFF

OFF

OFF

250

ON

OFF

OFF

125

OFF

ON

OFF

50

ON

ON

OFF

1000

OFF

OFF

ON

Setting the controller address
The switches S4L and S5L as well as the switches S1R to S4R correspond to certain values:

S4L

S5L

S1R

S2R

S3R

S4R

S5R

Value

1

2

4

8

16

32

-

In order to set the controller address, add up the values in a way that their sum equals the

controller address. Then set those switches to ”ON” whose values you have added up.
Example:
Setting the controller address 27
The sum of the values has to equal 27: 1 + 2 + 8 + 16 = 27
Ö

Switch setting:

S4L

S5L

S1R

S2R

S3R

S4R

S5R

ON

ON

OFF

ON

ON

OFF

-

Having set baud rate and controller address, fasten the front plate to the CAN addressing

module.