Commissioning – Lenze EMF2174IB User Manual

Page 11

Advertising
background image

Commissioning

EDK2174DB DE/EN/FR 3.0

11

Inbetriebnahme_en

Please note when switching on a controller for the first time:

Note!

ƒ

The parameter setting corresponds to the factory setting (baud

rate 500 kbaud, node address 1).

ƒ

If the controller is to operate with a baud rate other than 500 kbaud in a

CAN network, it may only be connected to the CAN network after having

been parameterised once with the help of the CAN addressing module.

Otherwise faults could occur during the initialisation of the controller in

the CAN network due to different baud rates.

Commissioning
1. Plug the CAN addressing module onto the automation interface (AIF) of the

controller.

2. After the initialisation of the controller, the CAN addressing module transmits the

coded baud rate and the controller address to the controller.

3. After the transmission, Reset Node (C0358) is automatically executed.
4. All parameters are permanently stored in the controller (C0003 = 1).
Operating states
The yellow LED indicates the state of the CAN addressing module:
ƒ OFF:

– The controller is not supplied with mains voltage.

ƒ BLINKING:

– An invalid controller address and/or

– baud rate has been coded.

ƒ ON:

– Error-free operating state

Advertising