Coding within the sub-d plug, Preliminary works – Lenze EMF2174IB User Manual

Page 9

Advertising
background image

Preliminary works

Coding within the Sub-D plug

EDK2174DB DE/EN/FR 3.0

9

H2WichtHinw-Codierung_DIP_en

Coding within the Sub-D plug

Via the 9-pin Sub-D socket of the CAN addressing module you can connect a coding plug

which defines baud rate and controller address of the basic controller.
In order to permanently set baud rate and controller address in the Sub-D plug, connect the

pins 1 to 8 to pin 9 in a certain way!

2174CAN004

Coding plug (view of the soldering side)

Setting the baud rate

Baud rate

Pin 1

Pin 2

Pin 3

[kbaud]

500

-

-

-

250

X

-

-

125

-

X

-

50

X

X

-

1000

-

-

X

”X”

= connect to pin 9

”-”

= do not connect

Example:
Setting the baud rate to 50 kbaud
Ö

Connect pin 1 to pin 9 and pin 2 to pin 9 by soldering.

Setting the controller address
You can calculate the connections between the pins 4 to 8 and pin 9 required for setting the

controller address by using the values of the following table:

Pin 4

Pin 5

Pin 6

Pin 7

Pin 8

Value

1

2

4

8

16

Example:
Setting controller address 13
The sum of the values has to equal 13: 1 + 4 + 8 = 13
Ö

Connect pins 4, 6 and 7 to pin 9 by soldering.