Electrical installation

Wiring with Application−I/O

EDK82ZBU DE/EN/FR 4.0

10

l

H1_E_INST−beisp_en

Wiring with Application−I/O

Setpoint selection through potentiometer and reversal of direction of rotation through
switch

Description of the functionality
ƒ Deceleration after STOP along the quick stop ramp (C0105).
ƒ Deceleration and acceleration after a reversal of the direction of rotation along

ramps C0013 and C0012.

For this, the following is required:
1. Connect the switch/potentiometer unit to the Application−I/O.
2. Configure hardware and software of the motec for a setpoint range of 0 ... 5 V:

– Adapt the jumper position at the function module.
– Adapt C0034.

3. Configure two digital inputs with the signals CW/QSP and CCW/QSP

Example for terminal configuration C0007 = −16−

7 7

X3

>100k

10k

A4 59 20 28 E1 E2 E3 E4 E5 E6

A2

A1

GND

+5V



1 = CW

2 = CCW

0

‚

0

2

1

min

max

2U 2I 62 63 9

1I

1U

>100k

GND

ƒ

A

C

B

D

E82ZBU03



Switch/potentiometer unit

‚

Wire bridge

ƒ

Setpoint selection possible via X3/1U or X3/2U

Wiring for setpoint selection through potentiometer

Wiring for reversal of direction of rotation through switch

CW

CW rotation

CCW

CCW rotation

Setpoint selection

Change of direction of rotation

Terminal
assignment

X3/1U
or
X3/2U

White wire

X3/20

Yellow wire
DC supply +20 V
Wire bridge to X3/28

Controller inhibit" (CINH)

X3/9:

Green wire

X3/E3

Grey wire = CW rotation
(CW/QSP on X3/E3)

X3/7

Brown wire

X3/E4

Pink wire = CCW rotation
(CCW/QSP on X3/E4)

Jumper position

Setpoint on X3/1U: Remove jumper A

Setpoint on X3/2U: Remove jumper B

Parameter setting

Setpoint on X3/1U: C0034/1 = −0−

C0007 = −16−

Setpoint on X3/2U: C0034/2 = −0−