Other application examples, Electrical installation – Lenze E82ZBU User Manual

Page 11

Advertising
background image

Electrical installation

Other application examples

EDK82ZBU DE/EN/FR 4.0

11

l

H1_E_INST−beisp_en

Other application examples

Starting/stopping (CINH) with the function module Standard−I/O



Switch/potentiometer unit

‚

Wire bridge

CINH

Controller inhibit

/CINH

Controller enable

Wiring for start/stop through switch

Terminal assignment

X3/20

Yellow wire
DC supply +20 V

X3/28

Grey wire
Start/stop

Pink wire = not used
Appropriate insulation!

Starting/stopping (CINH) with the function module Application−I/O



Switch/potentiometer unit

CINH

Controller inhibit

/CINH

Controller enable

Wiring for start/stop through switch

Terminal assignment

X3/20

Yellow wire
DC supply +20 V

X3/28

Grey wire
Start/stop

Pink wire = not used
Appropriate insulation!

)

Note!

Instead of using X3/28 also digital input (X3/E1 ... X3/E6) can be connected
and thus different digital functions, e.g. JOG1 on E1, can be activated.