4 technical data, 1 general data and operating conditions, Technical data – Lenze E82ZN User Manual

Page 29: General data and operating conditions, 4technical data

Advertising
background image

Technical data

General data and operating conditions

4

l

29

EDK82ZN903 DE/EN/FR 5.1

4

Technical data

4.1

General data and operating conditions

Standards

Approval

UL

UL 508, Standard for Electromagnetic Interference Filters
(File No. E219022) for USA and Canada

Mains data

Mains types

With grounded neutral (TT/TN systems)

Operation permitted without restrictions

Without grounded neutral

Max. mains voltage 400 V!
Observe instructions for special measures in the
documentation for the basic device!

IT systems

Operation is not permissible.

Protection

Type of protection

EN 60529

IP 20

Not in the wire range of
the terminals

NEMA 250

Protection against contact to
type 1

Insulation resistance

EN 61800−5−1

Overvoltage category III
> 2000 m: Overvoltage category II

Leakage current

EN 61800−5−1

> 3.5 mA

Observe regulations and
safety instructions!

Protective device

Type

Thermal contact, potential−free
NC contact

Function

Monitoring the internal
temperature of the device

Switching threshold

140 °C

Switching capacity

250 V / 1.6 A

Ambient conditions

Temperature

Storage

−25 ... +60 °C

Transport

−25 ... +70 °C

Operation

−10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C

Site altitude

0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m

Pollution

EN 61800−5−1

Pollution degree 2

Vibration resistance

EN 50178; IEC
61800−5−1;
Germanischer Lloyd,
general conditions

Acceleration−resistant up to 0.7 g

Advertising