2 connection plan, 3 connection data, Connection plan – Lenze E82ZN User Manual

Page 37: Connection data, Electrical installation

Advertising
background image

Electrical installation

Connection plan

6

l

37

EDK82ZN903 DE/EN/FR 5.1

6.2

Connection plan

L1

L1

L2

L2

T1

Load

Line

E82ZZ...

E82ZN...

8200 vector

9300 vector

9300 servo

L3

L3

T2

PE

PE

L3

N

PE

L1
L2

F1...F3

K1

4

J >

8200vec107

4 Integrate the thermal contact into the monitoring system so that the mains supply is switched off when the filter is

overheated.

6.3

Connection data

Type

"Line"

(Terminals L1/L2/L3)

"Load"

(Lines with ring cable lug)

Max. conductor

cross−section

Tightening torque

Æ

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

[Nm]

[lb−in]

E82ZZ15334B230

16

6

2 ... 4

17.7 ... 35.4

M6

See documentation on

basic device

E82ZN22334B230
E82ZN30334B230

35

2

2 ... 5

17.7 ... 44.3

E82ZN45334B230

50

1/0

2 ... 6

17.7 ... 53.1

M8

E82ZN55334B230

95

4/0

6 ... 12

53.1 ... 106.2

E82ZN75334B230

95

4/0

M10

E82ZN90334B230

120

250

10 ... 20

88.5 ... 177

Type

Thermostat (terminals T1/T2)

PE (stud bolt)

Max. conductor

cross−section

Tightening torque

Æ

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

[Nm]

[lb−in]

E82ZZ15334B230

4

28 ... 10

0.6 ... 0.8

5.3 ... 7.1

M6

5

44.3

E82ZN22334B230
E82ZN30334B230
E82ZN45334B230

M8

12

106.2

E82ZN55334B230
E82ZN75334B230

M10

23

203.6

E82ZN90334B230