Function block library lenzeelectricalshaft.lib – Lenze DDS Global Drive PLC Developer Studio User Manual

Page 14

Advertising
background image

Function block library LenzeElectricalShaft.lib

Special functions

2.1.1

Digital frequency ramp generator (L_DFRFG)

2−4

L

LenzeElectricalShaft.lib EN 1.2

2.1.1.3

Ramp generator stop

Maintains the state of the profile generator during operation.

·

Select the constant FIXED0% (selection number 1000) using bStop_b = TRUE, the function

ramp generator stop" is activated.

·

The latest state is output at nOut_v (16384

º 15000 rpm).

·

The set phase−angle detected at nIn_v is stored.

·

After reset of the Quickstop request, the set phase−angle is approached via the profile
generator.

t

n I n _ v

n M a x S p e e d

b S t o p _ b

t

n O u t _ v

Abb. 2−5

Diagram of the function ramp generator stop"

2.1.1.4

RESET

bReset_b= TRUE:

·

Resets the setpoint phase which has been internally summed up.

·

Activates the profile generator.

A TRUE−FALSE edge at bReset_b detects the set phase−angle.

2.1.1.5

Detect phase difference

Monitoring the phase−angle difference between nIn_v and nOut_v.

·

Select the constant FIXED0% (selection number 1000) using dwThresholdFollowingError to
adjust the limit for the monitoring (1

º 1 incr.).

·

If the monitoring is triggered, then bFail_b is set = TRUE.

·

Select the constant FIXED0% (selection number 1000) using bReset_b = TRUE to store the
signal.

·

The profile generator can accept a phase−angle difference of up to ±2140000000 incr.
(

» 32000 turns) (65536 º 1 turn).