Drive PLC
System blocks − FIF Standard−I/O
3.2
DIGITAL_IO_FIF (node number 200)
3−5
L
DrivePLC DE 6.0
3.2.2
Outputs_DIGITAL_FIF (digital outputs, "Standard I/O" FIF module)
This SB conditions a digital signal and transmits it to terminal A1 of the
Standard I/O FIF module.
A1
Outputs_DIGITAL_FIF
DIGOUT_bOut1_FIFSTDIO_b
C0479
Fig. 3−4
Outputs_DIGITAL_FIF
System variables
Variable
Data type
Signal type
Address
Display
code
Display
format
Notes
DIGOUT_bOut1_FIFSTDIO_b
Bool
binary
%QX200.0.0
C0479 − bit1
bin
Electrical data of the output terminal
Terminal
Use
Data
A1
freely assignable
Output voltage:
Output current:
0/+20 V with DC internal
0/+24 V with DC external
10 mA with DC internal
50 mA with DC external
Tip!
Detailed information about the terminal assignment for the Standard I/O FIF module can be found
in the corresponding Mounting Instructions!