Electrical installation
Wiring of system bus (CAN)
l
58
EDBPM−H315 DE/EN/FR 7.1
Terminal assignment
(
Stop!
Connect a 120
W terminating resistor to the first and last bus device.
Terminal
Identification
Explanation
1
V−
GND
Reference potential
2
CAN−
LO
System bus LOW (data line)
3
Shield
Connect the shield of the system bus cable
4
CAN+
HI
System bus HIGH (data line)
5
n.c.
Not connected
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type
Paired with shielding
Impedance
120
W (95 ... 140 W)
Cable resistance/cross−section
Cable length
£ 300 m £ 70 mW/m / 0.25 0.34 mm
2
(AWG22)
Cable length 301 1000 m
£ 40 mW/m / 0.5 mm
2
(AWG20)
Signal propagation delay
£ 5 ns/m