Electrical installation

Wiring of system bus (CAN)

4

l

58

EDBPM−H315 DE/EN/FR 7.1

Terminal assignment

(

Stop!

Connect a 120

W terminating resistor to the first and last bus device.

Terminal

Identification

Explanation

1

V−

GND

Reference potential

2

CAN−

LO

System bus LOW (data line)

3

Shield

Connect the shield of the system bus cable

4

CAN+

HI

System bus HIGH (data line)

5

n.c.

Not connected

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m