Selection tables for brake resistors – Lenze 6034 Brake chopper User Manual
Page 9
7
4.1.
Selection tables for brake resistors
Selection table for frequency inverters with a mains voltage of 190...260V (6032G):
Rated motor
power/kW
Brake resistor
Resistance/
Ω
Continuous power/W
Order no.
Article no.
0.37
470
50
ERBM470R050W
360115
0.75
200
100
ERBM200R100W
360114
1.5
100
150
ERBM100R150W
360113
2.2
82
200
ERBM082R200W
360112
Selection table for frequency inverters with a mains voltage of 330...450V (6033G):
Rated motor
power/kW
Brake resistor
Resistance/
Ω
Continuous power/W
Order no.
Article no..
0.75
470
100
ERBM470R050W
361839
1.5
370
150
ERBM370R150W
357872
2.2
240
200
ERBM240R200W
357874
3.0
180
300
ERBD180R300W
357875
4.0
100
600
ERBD100R600W
357876
5.5
82
600
ERBD082R600W
365902
Selection table for frequency inverters with a mains voltage of 370...510V (6034G):
Rated motor
power/kW
Brake resistor
Resistance/
Ω
Continuous power/W Order no.
Article no..
0.75
470
100
ERBM470R050W
361839
1.5
370
150
ERBM370R150W
357872
2.2
240
200
ERBM240R200W
357874
3.0
180
300
ERBD180R300W
357875
4.0
100
600
ERBD100R600W
357876
All brake resistors are equipped with integrated temperature
protection which must be used as safety protection (see pages 9
and 10).
When using other brake resistors, appropriate
overcurrent/overtemperature protection, e.g. thermal overcurrent
sensors etc. must be provided.