2 rated data, Rated data, Technical data – Lenze EZN3x0030H110 User Manual

Page 35

Advertising
background image

Technical data

Rated data

4

l

35

EDKZNXXXX−002 DE/EN/FR 3.0

4.2

Rated data

Basis of the data

Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

480

432 − 0 % ... 528 + 0 %

45 ... 65

Voltage

Frequency

Current [A]

Number of

phases

Type

[V]

[Hz]

up to +40 °C



up to +55 °C



EZN3x0110H030

400/480

50/60

30

18.75

3

EZN3x0080H042

400/480

50/60

42

26.25

3

EZN3x0055H060

400/480

50/60

60

37.50

3

EZN3x0037H090

400/480

50/60

90

56.25

3

EZN3x0030H110

400/480

50/60

110

‚

68.75

3

 Temperature in the control cabinet

‚ up to 35 °C: 130 A

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

DU [V]

EZN3A0110H030
EZN3B0110H030

110
135

1.10

10

EZN3A0080H042
EZN3B0080H042

144
180

0.80

10

EZN3A0055H060
EZN3B0055H060

160
155

0.55

10

EZN3A0037H090
EZN3B0037H090

170
160

0.37

10

EZN3A0030H110
EZN3B0030H110

220
220

0.30

10

Advertising
This manual is related to the following products: