4.3 Connection

4.3.1

Power connection

• All indications about cable cross-sections are

recommendations and refer to the application:
- in control cabinets and machines
- in cable ducts
- at a max. ambient temperature +40

°C

• The compliance with other standards (e.g.: VDE 0113, VDE

0289, etc.) remains the responsibility of the user.

• The cables between brake unit and controller must not be

longer than max. 2 m.

• If the brake unit is directly connected with the controller

and the cable length does not exceed

£ 0.5 m, the cables

can be used as unscreened single cores.

• For a radio interference suppression (limit-value class A or

B) to DIN 55011 observe the following:
- The cables must be screened.
- For cable lengths up to 1 m it is sufficient to connect the

screen at the middle.

- For cable lengths > 1 m, the screen must always be

connected on both sides.

Connection

• The cables between controller and brake unit must be

DC-bus connected to the terminals +UG, -UG.

• Observe stud torques:

Terminals

0.5 ... 0.6 Nm

e

a s

4.4 ... 5.3 lbfin