Beacon 200 Rig Monitor Operator’s Manual • 36

4. Screw the fixed flow regulator into the zero air calibration cylinder.

5. Use the calibration kit sample tubing to connect the fixed flow regulator

to the calibration cup/splash guard of the LEL detector.

6. Turn the regulator knob counterclockwise to open the regulator.

7. Allow zero air to flow for two minutes.

8. Turn the regulator knob clockwise to close the regulator. The Rig

Monitor will continue to display the minimum gas response on the
display and retain the response level in its memory.

9. Disconnect the sample tubing from the LEL detector and connect it to

the calibration cup/splash guard hose barb of the H

2

S detector.

10.Turn the regulator knob counterclockwise to open the regulator.

11.Allow zero air to flow for two minutes.

12.Turn the regulator knob clockwise to close the regulator. The Rig

Monitor will continue to display the minimum gas response on the
display and retain the response level in its memory.

13.Press the ENTER button at the Rig Monitor. The unit will adjust the

zero reading and display the message Fresh Air Adjust Passed for:
Channel 1 Channel 2
before continuing.

14.If you applied zero air to the detectors, unscrew the regulator from the

zero air calibration cylinder.

15.If you applied zero air to the detectors, leave the sample tubing

connected to the regulator and move it from the H

2

S detector to the LEL

detector’s calibration cup/splash guard.

If you did not apply zero air to the detectors, use the calibration kit
sample tubing to connect the fixed flow regulator to the calibration cup/
splash guard of the LEL detector.

NOTE: If the fresh air adjustment fails, see “Troubleshooting” on page 46

for recommended actions.

Adjusting the Span Setting

1. The display asks if you want to perform a span operation on channel 1

by applying gas. Press the UP/YES button to continue with adjusting
the span on channel 1.

If you press the DOWN/NO button, the unit will skip to channel 2.

2. The display asks if you want to perform a span operation on channel 2

by applying gas. Press the UP/YES button to continue with adjusting
the span on channel 2.