65-2399RK-CH4 Combustible Gas Transmitter • 17

4.

Turn the regulator’s on/off knob clockwise to close the regulator.

5.

Unscrew the regulator from the calibration cylinder.

Returning to Normal Operation

1.

Remove the voltmeter leads from the amplifier test points.

2.

Unscrew the calibration cup from the detector.

NOTE:

For convenience, leave the regulator and calibration cup connected by the
sample tubing.

3.

Secure the junction box cover to the junction box.

4.

When the controller display reading falls below the alarm setpoints, return the
controller to normal operation.

5.

Verify that the controller display reading decreases and stabilizes at 0 %Vol.

6.

Store the components of the calibration kit in a safe and convenient place.

Parts List

Table 6 lists replacement parts and accessories for the methane transmitter.

Table 6:Parts List

Part Number

Description

06-1248RK

Sample tubing (3/16 in. x 5/16 in.; specify length when ordering)

18-0400RK-01

Junction box with spacers

33-0157RK

Hydrophobic disk membrane for detector cap

57-1053RK

Amplifier with gasket (specify detector part number when ordering)

61-0199RK-CH4

Infrared CH

4

%Vol. detector

61-5041RK-CH4

Infrared CH

4

replacement plug-in sensor

65-2399RK-CH4

Methane transmitter (includes detector, junction box, and amplifier)

71-0201RK

65-2399RK-CH4 Methane Transmitter Operator’s Manual

(this document)

81-0013RK-01

Steel calibration cylinder, 50% Volume methane in nitrogen, 34-liter

81-0076RK-01

Steel calibration cylinder, zero emission air, 34-liter

81-1050RK

Regulator, 0.5 liter/minute; with pressure gauge and flow control knob, for 17 liter and
34 liter steel calibration cylinders

81-1103RK

Calibration cup

82-0006RK

Pot adjust screwdriver, for calibration