65-2399RK-CH4 Combustible Gas Transmitter • 3

Infrared CH

4

%Volume Detector

The infrared CH

4

%Vol. detector consists of the detector housing body, detector housing

cap, cap gasket, and the plug-in sensor.

Figure 2: Infrared CH

4

%Vol. Detector Component Location

Detector Housing Body

The detector housing body protects the electronic components within the housing. Use the
mounting threads at the top of the housing to screw the IR CH

4

detector into the 3/4”

NPT hub on the bottom of the junction box. Four color coded leads, red, white, green, and
black, extend from the other end of the detector. The leads allow you to connect the
detector to the amplifier.

The housing includes three sockets installed on a circuit board. These sockets accept the
plug-in sensor’s three pins to provide an electrical connection for the sensor. The circuit
board with the sockets conditions the sensor’s signal before the signal reaches the
amplifier.

Housing Cap & Cap Gasket

The housing cap screws onto the detector housing body. It retains the plug-in sensor and
protects it from damage. A foam gasket is installed inside the housing cap that seals
against the sensor face. A hydrophobic membrane on the outside of the cap face keeps
water and particulates away from the sensor face behind the cap. Unscrew the detector
cap to access the plug-in sensor for maintenance or replacement. A cap gasket seals the
interface between the housing body and cap.

Plug-In CH

4

Sensor

The plug-in sensor is secured in the detector assembly by the housing cap. The sensor pro-
duces a millivolt output that corresponds to the detection range of the transmitter.

Detector Housing Cap

Plug-In IR CH4
%Volume Sensor

Cap Gasket

Hydrophobic
Membrane

Detector Housing Body