Description, Amplifier controller terminal strip, J-box detector terminal strip – RKI Instruments 65-2399RK-CH4 User Manual

Page 6: Figure 1: methane transmitter component location

Advertising
background image

2 • 65-2399RK-CH4 Combustible Gas Transmitter

Description

The 65-2399RK-CH4 transmitter is calibrated to methane. The transmitter utilizes an
infrared type of detector which has some advantages over a catalytic type of combustible
detector. The infrared detector will generally have a longer service life than a catalytic
detector, it will require calibration less often, and it can detect methane even if there is no
oxygen in the sample which allows detection of methane in an inert atmosphere.

This section describes the components of the methane transmitter. The transmitter is a 4 -
20 mA type detector head. It consists of the methane detector, amplifier, and junction box.

Figure 1: Methane Transmitter Component Location

Amplifier

Controller Terminal Strip

G

LE

L

B

W

R

J-Box

Detector Terminal
Strip

S

PWR

/

S

IG

S

ens

or

C

u

rre

n

t

m

A

SP

A

N

Jumper Pins,

Factory Use Only

Factory Adjust Pot

Zero Pot

Span Pot

Factory Adjust Pot

IR CH4 %Volume
Detector

ZE

R

O

+ Test Point (Red)

100mV-500mV

Range

- Test Point (Black)

Advertising