Schwank ultraSchwank EIH User Manual

Page 11

Advertising
background image

11

UHE-F / EIH-F I&O Manual

IM100205

RD: MAY 2014

RL: 06A

MODEL

RECOMMENDED

MOUNTING

HEIGHT RANGE*

ft

(m)

MAXIMUM

DISTANCE

BETWEEN

HEATERS

ft

(m)

DISTANCE – OUTSIDE WALL

TO HEATER LONG AXIS

(PARALLEL TO WALL) IN “FEET”

HORIZONTAL

REFLECTOR

MOUNT

ft (m)

REFLECTOR

ANGLE

MOUNTED

UHE / EIH 200

20 – 40

(6 - 12)

50

(15)

17 – 25

(5 - 8)




COMBUSTIBLE

CLEARANCE

BEHIND

(refer to Table 1

& Figure 1)

UHE / EIH 160

18 – 30

(5 - 9)

45

(14)

15 – 20

(5 - 7)

UHE / EIH 130

16 – 25

(5 - 8)

40

(12)

15 – 20

(5 - 7)

UHE / EIH 90

14 – 22

(4.3 - 6)

30

(9)

12 – 16

(4 - 5)

UHE / EIH 60

12 – 20

(3.6 - 5.5)

25

(8)

11 – 15

(3.4 - 5)

TABLE 2 GUIDELINES FOR HEATER PLACEMENT - SPACE HEATING

IMPORTANT: Single or multiple heater placement must be such that continu-

ous operation of heater(s) will not cause combustible material or materials in

storage to reach a temperature in excess of ambient temperature plus 90F°

(50C°).

It is the installer’s responsibility to ensure that building materials with a

low heat tolerance which may degrade at lower temperatures are pro-

tected to prevent degradation. Examples of low heat tolerance materials

include vinyl siding, fabrics, some plastics, filmy materials, etc.

Refer to “Clearance to Combustibles” information on pages 6 to 8, and

Figure 1 and Table 1.

*

RECOMMENDED MOUNTING HEIGHTS are typical to provide optimum comfort in general

space heating applications. Variance to these typical heights can occur in some applications:



Higher mounting heights due to structure or application requirements



Lower mounting heights for area or ‘spot’ heat, or in areas with greater infiltration losses

(near overhead doors, etc)