Top view – Schwank ultraSchwank EIH User Manual

Page 23

Advertising
background image

23

UHE-F / EIH-F I&O Manual

IM100205

RD: MAY 2014

RL: 06A

H

ORIZONTAL

VENT

THROUGH

THE

SIDEWALL

:



The flue vent system must slope downwards approximately 1/4" per ft (63 mm/ 300 mm)
toward the vent terminal, starting at the termination of the radiant tube - radiant tube must
be level.



Install a minimum 36 inch (91 cm) length of minimum 26 gauge single walled 4” (10 cm)
diameter vent pipe at the end of the tube system, and a minimum 12 inch (30 cm) length
prior to fitting any Tee or Elbow



Seal all vent connections with high temperature sealant. Vent connections must be me-
chanically secured with three (3) #8 sheet metal screws uniformly spaced around the cir-
cumference of the vent pipe



When the vent pipe passes through a cold or unheated area where the ambient tempera-
ture is likely to produce condensation of the flue gases. The vent pipe shall be insulated
with a suitable material as approved and specified by the insulation manufacturer to with-
stand temperature up to 460°F (238°C)



The vent system must always be adequately supported to prevent sagging

FIGURE 15 - Heater Expansion - Vent Configuration

All Vent Pipe & Adapters By Others

FIGURE 16 - Horizontal Vent - ALL vent pipe and adapters by others

Clearances apply to Vent Terminal: 4” (10 cm) - JA-0528-XX Or 6” (15 cm) - JA-0529-XX

See notes below for use of other approved vent terminations

TOP VIEW

Advertising
This manual is related to the following products: