High altitude installation – Schwank ultraSchwank EIH User Manual

Page 45

Advertising
background image

45

UHE-F / EIH-F I&O Manual

IM100205

RD: MAY 2014

RL: 06A

MODEL

NO

STD

ORIFICE

Drill

Size /
Part#

FOR USE AT ALTITUDES ABOVE (FEET)

2000 3000 4000 5000 6000 7000 8000

UHE / EIH-

60N

26 DMS

JS-0726-DM

27 DMS

JS-0727-DM

9/64”

JS-0714-IN

28 DMS

JS-0728-DM

29 DMS

JS-0729-DM

29 DMS

JS-0729-DM

30 DMS

JS-0730-DM

30

JS-0730-DM

UHE / EIH-

90N

15 DMS

JS-0715-DM

17 DMS

JS-0717-DM

17 DMS

JS-0717-DM

18 DMS

JS-0718-DM

19 DMS

JS-0719-DM

19 DMS

JS-0719-DM

20 DMS

JS-0720-DM

22 DMS

JS-0722-DM

UHE / EIH-

130N

5.8 mm

JS-0758-MM

2 DMS

JS-0702-DM

7/32”

JS-0722-IN

3 DMS

JS-0703-DM

3 DMS

JS-0703-DM

4 DMS

JS-0704-DM

5 DMS

JS-0705-DM

7 DMS

JS-0707-DM

UHE / EIH-

160N

1/4”

JS-0725-IN

‘C’ Drill Size

JS-070C-NS

‘B’ Drill Size

JS-070B-NS

6 mm

JS-0760-MM

‘A’ Drill Size

JS-070A-NS

1 DMS

JS-0701-DM

1 DMS

JS-0701-DM

2 DMS

JS-0702-DM

UHE / EIH-

200N

‘N’ Drill Size

JS-070N-NS

‘M’ Drill Size

JS-070M-NS

‘L’ Drill Size

JS-070L-NS

‘L’ Drill Size

JS-070L-NS

9/32”

JS-0728-IN

7.0 mm

JS-0770-MM

I

’ Drill Size

JS-070

I

-NS

17/64”

JS-0726-IN

9000

1/8

JS-0713-IN

23 DMS

JS-0723-DM

9 DMS

JS-0709-DM

3 DMS

JS-0703-DM

‘G’ Drill Size

JS-070G-NS

ORIFICE - ALTITUDE CONVERSION CHART (see NOTES above)

When this appliance is installed above the stipulated altitude for the USA or Canada, the input

must be de-rated by 4% for each 1000 ft above the stipulated altitude. If your local utility sup-

plies gas with a de-rated heat content, no orifice change is required in the heater . Check

with your local utility regarding de-rating of this appliance.

USA: The factory installed orifice for this appliance is approved for altitudes zero to

2000 feet above sea level. When installed above 2000 feet, refer to the table above for

the correct orifice.

Canada: The factory installed orifice for this appliance is approved for altitudes zero to

4500 feet above sea level. When installed above 4500 feet, refer to the table above for

the correct orifice.

27. HIGH ALTITUDE INSTALLATION