8

5.

GAS CONVERSION:

NATURAL GAS or LP GAS

WARNING:

Conversion from one fuel gas to another shall only be done by a trained

and qualified gas service technician. Ensure all gas supply and heater components
are correct for the type of fuel gas in use.

Use only parts and components supplied by the manufacturer to accomplish conversion from one
gas type to another. Incorrect or improper conversion can result in personal injury, death, fire,
and/or property damage, and will void the product warranty.

Conversion from natural gas to LP gas

: Requires LP gas orifice (order JP-4009-OL-J from

manufacturer), conversion of gas control valve to LP gas (see below), and an LP pressure regula-
tor (field supplied) in the gas supply line

Conversion from LP gas to natural gas

: Requires natural gas orifice (order JP-4009-ON-J from

manufacturer), conversion of gas control valve to natural gas (see below), and a natural gas pres-
sure regulator (field supplied) in the gas supply line

1. Install the proper gas type orifice (see heater exploded view page 29)
2. Convert Gas valve:

 Conversion from NAT to LP (or

vice-versa) is accomplished by in-
verting the position of the conver-
sion screw in the gas valve body,
and replacing the orifice

 The conversion screw is marked

with “NAT ” on one end and “LP ’’
on the other end - the arrow “ ’’
indicates the end to be inserted
into the valve

 Ensure that the gas selection nip-

ple is seated firmly into the valve
body for the correct gas type

2. Check gas pressures:

 Ensure the gas supply pressure

regulator matches the gas type

 Check and set the gas supply

pressure to ensure a minimum 5”
w.c. natural gas (7” w.c. maximum) or minimum 11” w.c. LP gas (14” w.c. maximum)

 The heater manifold pressure can be checked at either of the side ports on the gas control

valve

 Remove one of the threaded plugs at the side of the valve
 Install a hose barb, connect and read manifold pressure with manometer
 The valve is factory-adjusted to 3.5” w.c. natural gas and 10.5” w.c. LP gas
 Replace threaded plug after confirming manifold gas pressure - use sealant on

threads

Conversion screw

Manifold gas
pressure
test port

3/8” FNPT gas supply

Gas type marked in

conversion screw