Reader setup – SDC E5 Series Access Control System User Manual

Page 3

Advertising
background image

In a networked system, each reader must be assigned a unique Terminal Address Number .
The factory default terminal address number of “01”. Follow the procedure below to change the
readers Terminal Address Number at each reader. Mark the reader’s name on the reference
chart (Page iv). You will enter the location later in the reader parameter section of the sofware on
the PC.

Reader Setup

Enter Programming

Mode

Press and Hold the ‘#” for
3 seconds

0. CHECK VERSION
1. SETUP

FUNCTION

PROCEDURE

DISPLAY WILL SHOW

Enter Setup

Enter “1”

PASSWORD:

Enter Password

Enter “1111” + “#”

1. ENROL 2. PASSWD
3. TIMER 4. SYSTEM

Select System Menu

Enter “4”

1. ALARM 2. MODE
3. COMM 4. OTHER

Select Communications

Menu

Enter “3”

1. ADDRESS 2. BAUD
3. FORMAT 4. RECO

Select Terminal Address

Menu

Enter “1”

1. ADDRESS : 01
. NEW:_

Enter New Terminal

Number

Enter “Terminal No.” + “#”
(for example “02”)

1. ADDRESS : 02
. NEW:_

Exit Programming Mode

Enter “#”

READY FOR CARD
####/## ##:##

PC

Front Door

Rear Door

Side Door

Terminal

Address

01

Terminal

Address

02

Terminal

Address

03

RS485/RS232 OR

RS485/USB

Converter

CONNECTING

E5P READERS

TO CREATE A

NETWORKED

SYSTEM

RS485 from readers

TR-

TR+

Each reader must have a separate Terminal Address

GND (-)

D-

D+

SG

P:\Installation Instructions\Access Controls\Inst-E5\INST-E5.vsd Rev C 03-13 Page: 2