When a E5P reader is being used with slave reader (such as the SDC E5PW or another HID
compatible Wiegand reader), the E5P must be configured to operate as a Master reader. Using the
keypad on the reader, follow the procedure below to configure the E5P to operate as a Master
reader.

Master/Slave Reader Setup

Enter Programming

Mode

Press and Hold the ‘#” for
3 seconds

0. CHECK VERSION
1. SETUP

FUNCTION

PROCEDURE

DISPLAY WILL SHOW

Enter Setup

Enter “1”

PASSWORD:

Enter Password

Enter “1111” + “#”

1. ENROL 2. PASSWD
3. TIMER 4. SYSTEM

Select System Menu

Enter “4”

1. ALARM 2. MODE
3. COMM 4. OTHER

Select Other Menu

Enter “4”

1. P_ZONE 2. E_ZONE
3. C_FREE 4. MORE

Select More Menu

Enter “4”

1. A_ZONE 2. ANTI_P
3. DURESS 4. MORE

Select More Menu

Enter “4”

1. READER 2. GUARD
3. TONE 4. PARK

Select Reader Menu

Enter “1”

1. MAIN 2. SUB
3. SWAP 4. HID

Select Sub Menu

Enter “2”

CURRENT: xxx
Press ‘1’

Change

Press ‘1’ until screen
shows CURRENT: HID

CURRENT: HID
Press ‘1’

Change

Press ‘#’

READY FOR CARD

####/##/## ##:##

Set slave reader

configuration to HID

Exit Programming Mode

PC

Front Door

(Entry)

Rear Door

Terminal

Address

01

Terminal

Address

02

RS485/RS232 OR

RS485/USB

Converter

CONNECTING A

SLAVE READER TO

AN E5P READER

RS485 from readers

TR-

TR+

Each master reader must have a separate Terminal Address

GND (-)

D-

D+

SG

Front Door

(Exit)

(Slave Reader)

(Master Reader)

P:\Installation Instructions\Access Controls\Inst-E5\INST-E5.vsd Rev C 03-13 Page: 3