Description of Functions
3-13
•
Low purchasing costs and cost-effective operation thanks to special
M2M-GPRS tariffs.
3.2
Functions of the interfaces
3.2.1 Digital inputs
Binary inputs for detection of external states as a high or low signal
•
Electrically isolated and floating in two groups:
•
Number:
8
•
Input voltage:
0 … 30 VDC
•
Input voltage status 0:
0 … 4 V / 0 … 1.2 mA
•
Input voltage status 1:
10 … 30 V / 1.5 … 4.5 mA
•
Debouncing can be parameterised
•
Each input can be assigned event-related texts with system text
blocks.
Equivalent circuit diagram for the digital inputs:
Each input can be assigned event-related texts with system text blocks,
see Section 4.6 Alarm Message.