2 functions of the interfaces, Description of functions, 1 digital inputs – Weidmuller GPRS Alarm Unit User Manual

Page 15

Advertising
background image

Description of Functions

3-13

Low purchasing costs and cost-effective operation thanks to special
M2M-GPRS tariffs.

3.2

Functions of the interfaces

3.2.1 Digital inputs

Binary inputs for detection of external states as a high or low signal

Electrically isolated and floating in two groups:

Number:

8

Input voltage:

0 … 30 VDC

Input voltage status 0:

0 … 4 V / 0 … 1.2 mA

Input voltage status 1:

10 … 30 V / 1.5 … 4.5 mA

Debouncing can be parameterised

Each input can be assigned event-related texts with system text
blocks.

Equivalent circuit diagram for the digital inputs:

Each input can be assigned event-related texts with system text blocks,
see Section 4.6 Alarm Message.