Digital outputs, Configuration – Weidmuller GPRS Alarm Unit User Manual
Page 48
Configuration
4-46
Debouncing time
•
The relevant input signal must have been present without
interruption for at least the set debouncing time for a message to be
triggered; shorter disturbances cannot trigger a message.
Text for High
•
A text that can be inserted into the message block using the text
block #VAL# or #DI1#...; thus, it is possible to modify the message
text dynamically, depending on the particular event.
•
Max. 16 characters.
Text for Low
•
A text that can be inserted into the message block using the text
block #VAL# or #DI1#...; thus, it is possible to modify the message
text dynamically, depending on the particular event.
•
Max. 16 characters.
Report
If you wish a message to be triggered via an input, it is imperative
that the appropriate input be set by
; .
Digital outputs
Switching time
•
The digital outputs can be switched by events (see Section 4.6
Alarm Message) "Switch if" and Section 4.9 Function control
"Switch if"
.
•
Switching time in seconds for which the output remains closed after
an event has occurred and before it reopens automatically
NOTE