3.5 Input Signal Connections

3.5.1 Digital/Pulse Inputs
Digital and pulse inputs share the same input channel. Each input is connected between the DIN

connector and COMMON. Inputs can be voltage-free contacts, NPN transistor switches, or a

TTL voltage signal (ON < 1.5 volt DC, OFF > 3.5 volts DC).

GND

WI-I/O-K

DIN1

DIN2

Inputs can be voltage free contact or

open-collector transistor

NPN

Inputs do not have any surge protection. If the sensor or switch is mounted a long way from the

WI-I/O K module, external isolation such as a relay may be required for surge protection.

3.5.2 Shaft Encoder Connections

COUNT

DIRECTION

GND

DIN2

DIN1

WI-I/O -K

PHASE 1

PHASE 2

GND

DIN2

DIN1

WI-I/O-K

INCREMENTAL SHAFT ENCODER

QUADRATURE SHAFT ENCODER

3.5.3 Analog Input
Current (mA) Input
The analog input has a positive and a negative terminal, and may be placed at any point in the

current loop, as long as neither input rises more than 27V above COMMON or ground. An

internal DC/DC converter provides 24 VDC 50mA supply for powering analog loops .