Weidmuller WI-I/O 9-K: Wireless I/O Transmitter v1.9 User Manual

Page 39

Advertising
background image

User Manual v1.9


Manual

WI-I/O 9-K

v1.9

Page 39

4.6 Supply Voltage

The supply voltage may be mapped as an internal analog input. The 16 bit value corresponds to

0-30V. There is no analog sensitivity for this measurement - it is only transmitted based on the

configured update time. The measurement is taken every time the WI-I/O K transmitter operates.

The supply voltage also has user-configurable setpoints to determine the Supply Low Volts

alarm. These setpoints can be set from the SetPoint option. The WI-I/O K module will shut-

down when the supply voltage reaches 90% of the “low volts” value. We recommend the

following setpoint values:

Battery Type

Low Volts Setpoint

Shut-down Voltage

WI-BP-I/O-9-K Battery Pack

6.0

5.4

12V “Gell-cell”

11.2

10.0

Advertising