Manual

WI-I/O 9-K

v1.9

Page 49

6.

Now adjust the signal to the maximum value (100%). Select “Process High Value”.

7.

When you have finished this process, select “Write Configuration” - this will write the

configuration values to the user-calibration registers in the WI-I/O K. Select “Done” and the

analog signal is calibrated.

The accuracy of the analog signal can only be

as accurate as the calibration. For high

accuracy measurement, you will need to use a

high accuracy mA or V meter to ensure that the

high and low values are correct.

If you wist to return to the factory-calibration,

select “4-20mA” at the AIN Range Selection

display, then “Clear Calibration” at the

“Analog Calibration” display.

5.3.4 Tone Reversals
This feature turns the radio transmitter on continuously for radio path testing. A series of 1 and 0

data bits is transmitted. If the WI-I/O K is powered from a battery supply, this testing will draw

a lot of power.

To do radio path testing, refer to the WI-I/O 9-x User Manual.

5.3.5 Firmware Version
The feature will display the firmware (software) version of the WI-I/O K module.