Weidmuller WI-I/O 9-L: Wireless I/O Transmitter / Receiver v1.3 User Manual
Page 79

WI-I/O 9-L Configuration Manual
WI-I/O 9-L Wireless I/O
page 79 of 108
$
"
%
"
!
WI Series lets you create your own customised thermocouple tables.
You may want to create your own thermocouple tables if the:
•
Configuration software does not support the type of thermocouple you want to use; or
•
You want to match the table to the calibration of a particular thermocouple sensor.
You should normally enter both cold-junction compensation tables and linearization tables for
your thermocouple type.
Note
If you are using an external cold-junction compensation circuit, set all the values in the cold junction
compensation table to 0 and disable cold junction compensation.
To create user-defined thermocouple tables:
1. Open the project.
2. Select the unit you want to change.
3. Select
Tables
.
4. Select
User-defined
thermocouple type:
5. You should normally select
Enable temperature compensation
. You should de-select
this option if you are using an external cold junction compensation circuit.
6. To change the table values, select the value you want to change: