Weidmuller WI-I/O 9-L: Wireless I/O Transmitter / Receiver v1.3 User Manual
Page 80

WI-I/O 9-L Configuration Manual
WI-I/O 9-L Wireless I/O
page 80 of 108
7. Enter the new value:
Fill the cold-junction table with the millivolt output of the thermocouple corresponding to each
10-degree temperature increment. Your thermocouple documentation should contain this
information.
The Linearization table lets you enter up to 51 data points relating the thermocouple voltage
to the desired output value.
You can enter the desired output value either as a milliamp value (range 0-20 mA) or as a
raw 16-bit unsigned value. Refer to Appendix A – Tables for translating different analog signal
types on page 104 for more information.
Note
You must enter the millivolt input values in ascending order; with the lowest millivolt
value entered into entry 1, and the highest in the last used entry.
Unused entries should be set to “100” millivolts.
8. WI Series writes the new thermocouple tables and settings to the module when you next
configure the module.