Weidmuller WI-I/O 9-L: Wireless I/O Transmitter / Receiver v1.3 User Manual
Page 82

WI-I/O 9-L Configuration Manual
WI-I/O 9-L Wireless I/O
page 82 of 108
Feature
Description
Example
Thermocouple warm up
time
The amount of time the analog circuits are
turned on before sampling the thermocouple
input.
For normal thermocouples, these can be set to
the minimum value (i.e. 0.08 seconds).
If using an external (millivolt) device powered
from the +24V supply that requires a longer
period to settle, you may need to set this value
to allow the external device to settle.
Unit temp sample period
The time between samples of the internal
temperature sensor.
The module temperature (Cold junction
temperature) is sampled every time the
thermocouple input is sampled. You will only
need to set this field if you want to sample the
temperature more often than you sample the
thermocouple, including when you are not
using a thermocouple.
Unit temp warm up time
The amount of time the analog circuits are
turned on before sampling the internal
temperature sensor.
You should always set this value set to the
minimum value (0.08 seconds).
Battery sample period
Time between samples of the internal supply
voltage.