Step 1: Remove Power
from the Drive

• Remove and lock-out all incoming power to the drive.

Step 2: Remove the
Protective Covers and Open
the Control Panel

1. Loosen, but do not remove, the four hexalobular screws that secure the top

protective cover to the drive, then slide the cover up and off the drive
chassis. Tightening torque is noted in the illustration for reassembly.

ATTENTION: Remove power before making or breaking cable
connections. When you remove or insert a cable connector with
power applied, an electrical arc may occur. An electrical arc can
cause personal injury or property damage by:

• sending an erroneous signal to your system’s field devices,

causing unintended machine motion

• causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.

L1

L2

L3

O

I

Tightening torque:
1.5 N•m (13 lb•in)

T15

=

AC current transducers located on
U and W terminals behind cover