Step 4: install the new ac current transducers – Rockwell Automation 20P PowerFlex DC Drive - Frame D AC Current Transducers User Manual

Page 6

Advertising
background image

Publication 20P-IN059A-EN-P

6

6. Remove the four M12 bolts and washers that secure each of the U and W

phase AC input terminal bus bars to the input bus bars and carefully slide
the terminal bus bars up until the AC current transducers can be removed
from the bus bars.

Step 4: Install the New AC
Current Transducers

Install the new AC current transducers in reverse order of removal as detailed in
Step 3:

Remove the Existing AC Current Transducers

above.

• Tightening torque for the M12 bolts is 45 N•m (398 lb•in).

• Verify that signal wire that was disconnected from the U and W phase bus

bars when removing the current transducers is re-installed.

Remove bolts and
washers from U and
W phase bus bars

Signal wire

U phase bus bar

W phase bus bar

Slide bus bars up until AC current
transducers can be removed