Status of operation, Status of operation -7 – Rockwell Automation 22-COMM-P PowerFlex Profibus Adapter User Manual
Page 15

Getting Started
1-7
The adapter uses three status indicators to report its operating status.
They can be viewed through the drive cover. See
Figure 1.2 Status Indicators (location on drive may vary)
Status of Operation
Item Status
Indicator
Status
(1)
(1)
If all status indicators are off, the adapter is not receiving power. See
, for instructions on installing the adapter. If any other conditions occur, see
Description
➊
PORT
Green
Normal Operation. The adapter is properly connected and
is communicating with the drive.
Flashing
Green
Not used
➋
MOD
Green
Normal Operation. The adapter is operational and is
transferring I/O data.
Flashing
Green
Normal Operation. The adapter is operational but is not
transferring I/O data.
➌
NET A
Green
Normal Operation. The adapter is properly connected and
communicating on the network.
Flashing
Green
Not used
➍
NET B
Off
Not used for Profibus adapter.
➊
➋
➌
➍
➊
➋
➌