Install components – Rockwell Automation 20B PowerFlex 700 Drives - Frame 10 Components Replacement User Manual
Page 57
 
Rockwell Automation Publication 20B-IN026B-EN-P - July 2013
57
Inverter Assembly Component Replacement Procedures
Chapter 3
Install Components
1. Carefully examine the Transitional Busbar Assembly and Bus Capacitors
for damage.
When replacing any IGBT module, we recommend that you replace all 
Bus Capacitors. If needed, see 
to replace
damaged Bus Capacitors.
2. Install the IGBT module.
a. Use isopropyl alcohol to thoroughly clean the surface of the Heatsink.
b. Verify that the mounting surface of the new IGBT module is clean. If 
not, clean the mounting surface with isopropyl alcohol.
c. Use a 3- or 4-inch paint roller or putty knife to apply a thin even coating
of the supplied thermal grease to the mounting surface of the IGBT 
module.
In the next step, take care to not disturb any of the thermal grease on the 
IGBT module. 
d. Place the IGBT on the chassis with the serial number label at the top.
Install with supplied screws using this torque sequence:
IMPORTANT
If the Transitional Busbar Assembly was not removed, take care to not 
damage the Flexible Capacitor Busbars fitting over and under the 
Transitional Busbar Assembly.
➑
➋
➍
➏
➎
➌
➊
➐
IGBT Torque Sequence
First Sequence: 0.7 N•m (6.0 lb•in)
Second Sequence: 1.5 N•m (14 lb•in)
Final Sequence: 5.6 N•m (50 lb•in)
IMPORTANT
The three positive (+) Flexible Capacitor Busbars supplied with the kit must 
be installed on the back side of the Transitional Busbar Assembly before 
they can be installed on the IGBT. See page 
for how to install these
busbars on the Transitional Busbar Assembly.