Step 5: install the new pulse transformer board – Rockwell Automation 20P PowerFlex DC Drive - Frame C Pulse Transformer Circuit Board User Manual

Page 14

Advertising
background image

14

Rockwell Automation Publication 20P-IN010C-EN-P - February 2012

PowerFlex DC Drive Frame C Pulse Transformer Circuit Board

Step 5: Install the New

Pulse Transformer
Board

Install the new Pulse Transformer board in reverse order of removal as detailed in
Step 3:

Remove the Existing Pulse Transformer Board on page 4

.

1. Inspect the existing connection cables for burn marks, cracks or loose

connectors. If necessary, replace the cables connected to connector X3, X4,
X5, XCD, XR, XSW, XTA and XUVW on the Pulse Transformer board
with the new cables provided.

2. Inspect the existing gate lead cables for burn marks, cracks or loose

connectors. If necessary, replace the gate lead cables with the new cables
provided.

Step 6: Replace the

Protective Covers
and Documenting
the Change

1. Replace the protective covers in the reverse order of removal as described

in Step 2:

Remove the Protective Covers on page 3

.

2. Install DPI cable (if present).
3. Record the installation of the new Pulse Transformer board and date of

installation on the Field Installed Option label on the side of the drive (as
shown below).

ATTENTION: Each gate lead cable must be connected to the exact connector
from which it was removed on the Pulse Transformer circuit board or damage to
the drive may occur.

Advertising