Rockwell Automation 22-COMM-L LonWorks Adapter User Manual
Page 39

Configuring the Network
4-11
Variable: nvoAnalogInput1
Format: SNVT_lev_percent
Explanation: This Network Variable Output provides the status of drive
analog input 1.
PowerFlex 40 Drive Parameter Equivalent: Parameter d020 - [Analog
In 0-10V]
PowerFlex 400 Drive Parameter Equivalent: Parameter d305 -
[Analog In 1]
Variable: nvoAnalogInput2
Format: SNVT_lev_percent
Explanation: This Network Variable Output provides the status of drive
analog input 2.
PowerFlex 40 Drive Parameter Equivalent: Parameter d021 - [Analog
In 4-20mA]
PowerFlex 400 Drive Parameter Equivalent: Parameter d306 -
[Analog In 2]
Variable: nvoDigInput1
Format: SNVT_switch
Explanation: This Network Variable Output provides the status of drive
digital input 1 via Logic Status word bit 12 (see
Analog Input 1 Status
Analog Input 2 Status
Digital Input 1 Status
nvoDigInput 1 Variable
Status
Value (%)
State
0.0
0
Input 1 Disabled
100.0
1
Input 1 Enabled