Troubleshooting

5-3

The NET A status LED indicates the status of the LonWorks interface.

If you encounter unexpected communications problems, diagnostic
items can help you or Allen-Bradley personnel troubleshoot the problem.
The following diagnostic items can be accessed using DriveExplorer
software (version 3.01 or higher), DriveExecutive software (version 3.01
or higher), or a PowerFlex 4-Class HIM (22-HIM-*).

NET A Status Indicator (Service Indicator)

State

Cause

Corrective Actions

Off

The node is configured.

No action required.

Solid
Green

The node has no application
program.

The Neuron Chip must be loaded with a new
application program.

Flashing
Red

WINK command received.

No action required.

Flashing
Green

The node is not configured.

Configure the node.

Adapter Diagnostic Items

No. Name

Description

1

Last Reset Cause

0 = Power Up
1 = External
2 = Watchdog
3 = Software
4 = Cleared

2

LON Recv Err

Lon CRC errors detected during packet reception.

3

LON Lost Msg

Number of incoming packets that have been discarded due to
no available application buffers.

4

DSI CRC Errors

Current value of faulty DSI messages.

5

DSI Messages

Current value of valid DSI messages.

6

Neuron Error

Most recent error logged by the system in the Neuron Chip.
See

System Events on page 5-5

for code numbers and

descriptions.

7

Reference

Current value of the product-specific Reference being
transmitted to the host by this adapter.

8

Feedback

Current value of the product-specific Feedback being received
from the host by this adapter.

9

Logic Cmd

Current value of the product-specific Logic Command being
transmitted to the host by this adapter.

10 Logic Sts

Current value of the Common Logic Status being received from
the host by this adapter.

11 Number of Events

Number of events in the event list.

Advertising