Rockwell Automation 22-COMM-L LonWorks Adapter User Manual
Page 44

4-16
Configuring the Network
NCI: nciRampUpTm
Format: SNVT_time_sec
Explanation: This Network Configuration Input sets the acceleration
time. The value specifies the length of time it will take to bring the
inverter from stop to maximum frequency.
Valid Range: 0.0 - 600.0 seconds
Default Value: 10.0 seconds
PowerFlex 40/400 Drive Parameter Equivalent: Parameter P039 -
[Accel Time 1]
NCI: nciRampDownTm
Format: SNVT_time_sec
Explanation: This Network Configuration Input sets the deceleration
time. The value specifies the length of time it will take to bring the
inverter to a stop when running at maximum frequency.
Valid Range: 0.1 - 600.0 seconds
Default Value: 10.0 seconds
PowerFlex 40/400 Drive Parameter Equivalent: Parameter P040 -
[Decel Time 1]
NCI: nciLocation
Format: SNVT_str_asc
Explanation: This Network Configuration Input can be used to set the
physical location of the object in text. That is, it can hold the building,
level, and room descriptor. A maximum of 31 characters can be entered.
Default Value: Empty spaces
Ramp Up Time
Ramp Down Time
Location