Circuit diagram, Terminal connections, Circuit diagram terminal connections – Rockwell Automation 440R-S845AER-NNL MSR57P GuardMaster Speed Monitoring Safety Relay User Manual

Page 4

Advertising
background image

4 GuardMaster MSR57P Speed Monitoring Safety Relay

Publication 440R-IN016B-EN-P - November 2008

Circuit Diagram

Terminal Connections

Terminal

Function

A1

+24V dc, user supply

A2

Common, user supply

S11, S21

Test_Out_0, Test_Out_1, pulse test outputs for safety functions

S12, S22

SS_In_Ch0, SS_In_Ch1, Safe Stop (SS) dual-channel input

S72, S82

ESM_In_Ch0, ESM_In_Ch1, Enabling Switch Monitor (ESM) dual-channel input

S52, S62

SLS_In_Ch0, SLS_In_Ch1, Safe Limited Speed (SLS) dual-channel input

S32, S42

DM_In_Ch0, DM_In_Ch1, Door Monitor (DM) dual-channel input

X32, X42

LM_In_Ch0, LM_In_Ch1, Lock Monitor (LM) dual-channel input, solenoid position

Y1

24V dc output for reset (S34) and for feedback (Y2)

S34

Reset_In

Y2

RL_In, feedback input

Y35

SLS_Status output

Y37

Fault_Status output

13

Supply power for Motion Power (MP) safety outputs 14 and 24

14, 24

MP_Out_Ch0, MP_Out_Ch1, Motion Power (MP) outputs

68, 78

SLS_Out_Ch0, SLS_Out_Ch1, Safe Limited Speed (SLS) outputs

51

DC_Out_Ch0 (High Side), Door Control output [door switch solenoid, bipolar or cascading

(1)

]

(1)

The DC_Out output may also be configured as cascading (2 Channel Source). For information on using this configuration in
limited applications, refer to the GuardMaster Speed Monitoring Safety Relay User Manual, publication 440R-UM004.

52

DC_Out_Ch1 (Low Side), Door Control output [door switch solenoid, bipolar or cascading

(1)

]

34, 44

SS_Out_Ch0, SS_Out_Ch1, cascading Safe Stop outputs

Y31

24V dc power for isolated outputs

Y32

Stop_Command, isolated output

Y33

SLS_Command, isolated output

Y30

GND for isolated outputs

DPI

RJ45-1

Y1

S34

Y2

Y31 Y32 Y33 Y30

Mini-DIN

34

44

14

24

78

68

Y37

Y35

RJ45-2

A1

51

A2

52

S11 S21

S32 S42

13

X32 X42

S72 S82

S12 S22

S52 S62

HIM

51

52

Pulse

Test

Outputs

Safe
Stop

(SS_In)

Safe

Limited

Speed

(SLS_In)

Enabling

Switch

(ESM_In)

Door

Monitor
(DM_In)

Lock

Monitor

(LM_In)

Monitor
Encoder

PS

24V dc

Res

et_In

Feed

back

(RL

_

In)

24V dc

GN

D

Stop_Com

m

and

SL

S_Com

m

and

Isolated Outputs

Diag.

Out

Door Lock

Control

(DC_Out)

bipolar

SL

S_Status

Faul

t_St

at

us

Hi

Lo

SS_Out

(Cascade)

Motion

Power

(MP_Out)

2 OSSD

Enc

oder

1

En

co

de

r 2

SLS_Out

(Cascade)

2 OSSD

2 OSSD

Door Lock

Control

(DC_Out)

Cascade

Hi

Hi

Advertising