Environmental Specifications

Attribute

Value

Temperature, operating -5…55 °C (23…131 °F)

Relative humidity

90% RH noncondensing

Vibration

10…55 Hz, 0.35 mm displacement

Shock, operating

10 g, 16 ms, 100 shocks

ESD immunity

4 kV contact discharges; 8 kV air discharges

Radiated RF immunity

10 V/m from 80…1000 MHz; 3 V/m from 1.4…2.0 GHz;

1V/m from 2.0…2.7GHz

EFT/B immunity

Power, dc: ±2 kV
I/O signal lines: ±1 kV

Surge transient immunity Power, dc: ±0.5 kV line-line and ±0.5 kV line-earth

I/O signal lines: ±1 kV line-earth

Conducted RF immunity 10V rms from 150 kHz…80 MHz

Certifications

Certification

(1)

Value

c-UL-us

UL Listed, certified for US and Canada.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions.

EN 61131-2 Programmable Controllers (Clause 8, Zone A & B).

EN 61326-3-1; Meas./Control/Lab., Industrial Requirements.

EN 61000-6-2; Industrial Immunity.

C-Tick

Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions.

TÜV

TÜV Certified for Functional Safety: SIL CL1 to CL3, according to IEC 61508/EN62061;
Category 1 to 4 and Performance Level e, according to EN ISO 13849-1, when used as
described in the GuardMaster MSR57P Speed Monitoring Safety Relay User Manual,
publication 440R-UM004.

(1)

When product is marked. See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and