Bulletin 161
6
4.1 Connection and description of the power terminals
The control unit must be open in order to be able to wire the power terminals. Do not apply mains voltage to the
drive connection terminals U/T1, V/T2, and W/T3 as this will result in damage to equipment. The Bulletin
161 drives feature an electronic overload protection to monitor the drive current. In the case of multi-motor
operation, thermal contacts or PTC resistors must be used for each motor. In the case of motor lead lengths >
50 m motor reactors should be used.
Connection example Bulletin 161
AC Line Input fuse ratings or other Line Side Protective Devices:
Fuse Rating
Circuit Breaker Type and Rating
Bulletin 161S-AA01 – AA03
: 10 A time-lag
140-MN-1000 / 140M-D8N-C10
Bulletin 161S-AA04 – AA07
:
16 A time-lag
140-MN-1600 / 140M-D8N-C16
Bulletin 161S-AA10
:
25 A time-lag
140-MN-2500 / 140M-D8N-C25
Mains power supply
Connection for optional
brake chopper
Bulletin 161
Line filter EMC