Accessories, Line filter module specifications, Filter dimensions (mm) – Rockwell Automation 161 SERIES A User Manual
Page 35

Bulletin 161
29
10. Accessories
Line Filter Module
Specifications
Line Filter
Module
Nominal
Voltage
[V]
Nominal
Current
at 40°C
[A]
Leakage
Current
at 50 Hz
(mA)
Test voltage
[VDC for 2s]
ph. / ph;
ph. / ground
Input wire
max. cross
section
[mm2]
Output cable
cross section
[mm2]
Heat
dissipation
[W]
161S-RFA-6-A
240 +5%
2 x 6 A
< 3,5
1400 / 2800
(L) 4/4 (N)
3x1.5
5
161S-RFA-9-B
240 +5%
2 x 10 A
< 3,5
1400 / 2800
4/4
3x1.5
6
161S-RFA-22-C
240 +5%
2 x 23 A
< 10
1400 / 1400
4/4
3x2.5
9
Current:
at 40°C ambient temperature
Overload:
150% IN for 10 min
Frequency:
50 / 60 Hz
Material:
steel, surface refined
Humidity class:
C
Operation height:
< 1000 m without derating
> 1000 m, IN-2%, for each 1000m
Temperature range:
-25°C to +85°C
Connections
Input terminals IP 20 and PE-screw M5
Load side: cable, unshielded
Dependence of current on ambient temperature
0
0 , 2
0 , 4
0 , 6
0 , 8
1 , 0
2 0
4 0
6 0
8 0
1 0 0
T
i
°C
0
I
B
I
N
1 , 2
Filter Dimensions (mm):
F
D A
E
B
C
type 1
Line Filter Module
A
B
C
D
E
F
161S-RFA-6-A
120
80
25
110
67
2x6
161S-RFA-9-B
130
110
27
118
98
4x6
161S-RFA-22-C
180
140
29
168
128
4x6
temperature in °C