Rockwell Automation 161 SERIES A User Manual
Page 24

Bulletin 161
18
Parameter
number
Function
Basic
value
Setting range
Input
V/F characteristics / boost
A41
Boost select
00
00: Man. boost
01: Auto boost
A42
Manual boost
11
0 – 99
A43
Max. boost at % of base frequency
10
0 - 50%
A44
V/F select
00
00: Constant
01: Variable
A45
Maximum output voltage
100
50 - 100%
DC brake
A51
DC Brake active / inactive
00
00: inactive
01: active
A52
DC Brake
Starting frequency
0.5
0.5 – 10 Hz
A53
DC Brake
Waiting time
0.0
0 - 5 s
A54
DC Brake
Braking torque
0
0 - 100%
A55
DC Brake
Braking time
0.0
0 - 60 s
Operating frequency range
A61
Maximum Frequency
0.0
0.5 - 360 Hz
A62
Minimum Frequency
0.0
0.5 - 360 Hz
A63
1
st
Skip Frequency
0
0 - 360 Hz
A64
1
st
Skip Frequency Band
0.5
0 - 10 Hz
A65
2
nd
Skip Frequency
0
0 - 360 Hz
A66
2
nd
Skip Frequency Band
0.5
0 - 10 Hz
A67
3
rd
Skip Frequency
0
0 - 360 Hz
A68
3
rd
Skip Frequency Band
0.5
0 - 10 Hz