Rockwell Automation 25-COMM-E2P PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter User Manual
Page 58

58
Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Chapter 4
Configuring the I/O
3.
Edit the following information about the drive:
4.
Under Connection Parameters, edit the following:
Enter the number of 16-bit words that are required for your I/O in the
Input Size and Output Size boxes. Since the adapter always uses the 16-bit
Logic Status, 16-bit Feedback, and two 16-bit words dedicated for
memory allocation of the Generic Ethernet module profile, at least four
16-bit words must be set for the Input Size. The adapter also uses the 16-
bit Logic Command and 16-bit Reference, requiring at least two 16-bit
words for the Output Size. If any or all of the drive’s eight 16-bit Datalinks
are used (see
Configuring a Master-Slave Hierarchy on page 33
), the Input
and Output Size settings must be increased accordingly.
Box
Setting
Name
A name to identify the drive.
Description
Optional – description of the drive.
Comm Format
Data – INT (This setting formats the data in 16-bit words.)
IP Address
The IP address of the drive.
Open Module
Properties
When this box is checked, clicking OK opens additional module properties screens to
further configure the drive. When unchecked, clicking OK closes the drive’s New
Module screen. For this example, check this box.
Box
Assembly Instance
Size
Input
1 (This value is required.)
The value will vary based on the total number of Host
parameters [Opt Data In x] used for your application,
either in Single-drive mode (see details below) or Multi-
drive mode (see
Using Multi-Drive Mode on page 87
Output
2 (This value is required.)
The value will vary based on the total number of Host
parameters [Opt Data Out x] used for your application,
either in Single-drive mode (see details below) or Multi-
drive mode (see
Using Multi-Drive Mode on page 87
Configuration
6 (This value is required.)
0 (This value is required.)