Configuring the I/O

Chapter 4

Generic Profile Example of I/O Image

For the example below, all four [Opt Data In x] and all four [Opt Data
Out x]

parameters are used, resulting in an Input Size of “8” and an

Output Size of “6.”

5.

After setting the information in the drive’s New Module window, click
OK

. The Module Properties window appears.

IMPORTANT

The Host Datalink parameters [Opt Data In x] and [Opt Data Out x] do
not actually contain data. These are user-configurable parameters that
only contain the parameter number of the parameter whose data will
be made available for write/read in the I/O image. See

Using Datalinks

on page 66

.

Adapter

Word and I/O

Logic Command

Word 0

Reference

Word 1

Datalink 1

Word 2

Datalink 2

Word 3

Datalink 3

Word 4

Datalink 4

Word 5

Logic Status

Word 2

Feedback

Word 3

Required

Padword

(1)

Word 0

Padword

Word 1

Datalink 1

Word 4

Datalink 2

Word 5

Datalink 3

Word 6

Datalink 4

Word 7

Optional

Required

Optional

Output

Image

(Write)

Input

Image

(Read)

(1) Padwords only apply when using the generic profile. Padwords are not used when using the full-featured drive Add-

On-Profile.