Pub #75054-004-08, March 2013

OUT/OUT2

Output/Output 2

Switching mode

HYNO:
Hysteresis/NO
contact
HYNC:
Hysteresis/NC
contact
WINO:
Window/NO contact
WINC:
Window/NC contact
4...20 mA:
Analog mode (analog
output versions only)

Switch point
value

Switch point
0.5...100% URL in
increments of 0.1

°

C

Reset point value

Reset point 0...99.5%
URL in increments of
0.1

°

C

Switch point
delay

Delay time 0...99 sec.
in increments of
0.1 sec.

Reset point delay

Delay time 0...99 sec.
in increments of
0.1 sec.

Min. distance between SP and RSP:0.5°C/K (0.9°F)