837E Solid-State Temperature Sensors User Manual

Operation

18

Pub #75054-004-08, March 2013

Service Function Setting

SERV

Service Functions

Security
locking/password
protection

Enable password
protection

Password/code
entry

Select code 1...9999
0 = no locking

Reset

Reset all entries to
the factory setting

Revision counter

Increases by 1 with
each configuration

Last device status

Displays the last
device status to
occur

0

Simulation
output 1 or 2

OFF: No simulation
OPEN: Switch
output open
CLOS: Switch
output closed
3.5: Simulation
values for analog
output in mA
(3.5/4.0/8.0/12.0/16
.0/20.0/21.7)

Max. indicator

Display of max.
measured
process value

Min. indicator

Display of min.
measured
process value